Definitions
IEC 60085 defines a classification system that specifies the highest allowable temperature that the electrical insulating material can handle continuously without reducing its lifespan, in this case for the motor windings. If the temperature rise limits are exceeded for the windings, the insulation will degrade at a faster rate. This article focuses on Class B, F and H, as these are more applicable for typical industrial motors. For every 10°C increase in temperature, it is estimated that the degradation rate will double, i.e. average lifespan will be halved.
For motors of output less than 5000kW, IEC-60034-1 defines the limits of temperature rise of windings (indirectly cooled by air). These limits take reference from an ambient room temperature not exceeding 40°C, altitude of less than 1,000m above sea level (a.s.l.), and for a motor operating at 1.0 service factor. The thermal classes and respective limits in temperature rise are shown in Table 1.
| Letter Designation | Thermal Class (°C) | Limit of Temperature Rise of Winding (K/°C) |
|---|---|---|
| B | 130 | 80 |
| F | 155 | 105 |
| H | 180 | 125 |
Table 1: Limits of Temperature Rise of Windings
Winding Temperature Rise by Resistance Method
One way of measuring the winding temperature is by the resistance method. Copper wire changes its electrical resistance based on changes in temperature, with respect to the temperature coefficient of resistance. As the resistance method gives the average temperature for the winding, the industry practice is to add around 10 to 15K to estimate the hot-spot temperature, which can be measured by other means, typically by thermometer method or an Electronic Temperature Device. The hot-spot temperature will be used as the reference to the highest allowable temperature for each class.
To calculate the hot winding temperature (T₂), a set of cold baseline measurements and a hot measurement right after stopping the motor are taken:
where:
234.5: Constant value, derived by taking the reciprocal of the temperature coefficient of resistance for copper at 0°C (approximately 0.00427/°C).
Baseline (cold) measurements:
T₁: Ambient thermometer temperature when the motor is cold.
R₁: Initial resistance measurement when at temperature T₁.
R₂: Hot winding resistance measured right after shutdown.
T2 - T₁: Winding temperature rise
Maximum Temperature Rise of Motor Winding
Based on the maximum winding temperature for each thermal class, the respective maximum temperature rise of the motor windings can be determined by subtracting the baseline maximum ambient temperature of 40°C, and the hot-spot temperature variation of 10 to 15K, to derive the rise for each class as illustrated in Figure 1.

Changes in Altitude
For motors operating up to 1,000m a.s.l., the maximum ambient temperature is taken as 40°C, with the respective maximum winding temperatures for each class as shown in the earlier section. According to IEC 60034-1, there is no adjustment to the respective limits in temperature rise for altitudes between 1,000m to 4,000m a.s.l., where it is assumed that although an increased altitude brings about a cooler ambient temperature as shown in Table 2, it is compensated by a reduction in motor cooling due to the lower air density. Consequently, changes in altitude are not expected to change the limits in temperature rise for winding.
| Class B | Class F | Class H | |
|---|---|---|---|
| Max. Winding Temp. | 130°C | 155°C | 180°C |
| Altitude (m) | Assumed Maximum Ambient Temperature (°C) | ||
| 1,000 | 40 | 40 | 40 |
| 2,000 | 32 | 30 | 28 |
| 3,000 | 24 | 19 | 15 |
| 4,000 | 16 | 9 | 3 |
Table 2: Assumed Maximum Ambient Temperature against Altitude
Service Factor (S.F.) and Motor Surface Temperature
The temperature rises are based on a motor operating at 1.0 S.F. in accordance with IEC standards. There is also the NEMA standards (North America) that designates a multiplier to the rated output power, typically 15%, that defines that a motor with 1.15 S.F. can operate for short durations with an overload up to 15% over its rated output power. This also results in a higher allowable temperature rises for the winding by 10°C (for Class B & F).
From industry practice, the surface temperature of the motor is around 15 to 30K lower than the interior of the windings.
Taking into account of the above scenarios, the summarised temperature limits are:
| Class | Max. Temp. Rise (K) | 1.0 S.F. | 1.15 S.F. | ||
|---|---|---|---|---|---|
| Max. Winding Temp. (°C) | Surface Temp. (°C) | Max. Winding Temp. (°C) | Surface Temp. (°C) | ||
| B | 80 | 130 | 100-115 | 140 | 110-125 |
| F | 105 | 155 | 125-140 | 165 | 135-150 |
| H | 125 | 180 | 150-165 | - | - |
Table 3: Limits of Temperature Rise of Windings
Motor Designed with Class F Insulation and Operating within Class B Temperature Rise
After studying the motor insulation classes and respective limits placed on the winding temperature rise, we see that it is possible for a motor to be designed with enhanced life expectancy and reliability, through increasing the safety temperature margin that the motor is designed to operate in. One typical industry practice is to design the motor to be used with Class F electrical insulating materials, while operating at typical loads that fall within the temperature rise of 80K for Class B. Such motors are typically rated as F/B, and have a safety margin of 25K as illustrated in Figure 2.